Fleck 5800 and 5810 piston kits use different part-number families, and flow direction remains part of the selection. Do not select by controller appearance or by “58xx” alone.
Exact kit comparison
| Valve | Configuration | Documented kit |
|---|---|---|
| Fleck 5800 | Downflow | 61837 piston and seal kit |
| Fleck 5800 | Upflow | 61838 piston and seal kit |
| Fleck 5810 | Downflow | 61956-01 piston, seal, and spacer kit |
| Fleck 5810 | Upflow | 61956-02 piston, seal, and spacer kit |
| Fleck 5810 | Filter | 61956-03 piston, seal, and spacer kit |
5812 is not automatic
The 5810 and 5812 share a service manual, but they remain distinct body configurations. Infer 5812 fitment only when the exact part row explicitly lists it. The 61919 1-1/4-inch meter assembly, for example, still requires meter size and connection confirmation.
Use the 5800 hub and 5810 hub after reading the body label and flow direction.
Service safety and limits
These checks identify a valve and narrow a parts search; they are not a substitute for the manufacturer service procedure. Before opening a valve, use the documented bypass procedure, isolate water, relieve pressure, and disconnect power. Water-treatment valve service should be performed by a qualified person. Stop if the label, flow direction, wiring, or part suffix does not match the cited manual.
Primary sources
- Pentair Fleck 5800SXT Service Manual, document 43359-01, service-parts tables.
- Pentair Fleck 5810/5812SXT Service Manual, document 44019, piston and meter tables.
Revision status: no superseding revision is asserted. Verify the revision block in the linked manufacturer document. Evidence reviewed September 28, 2026.